Greenhouse Ventilation Calculator

One air change a minute is the summer target. Enter your greenhouse size and get the fan CFM for summer, shoulder season, and winter, plus inlet area.

By

| Published on

Greenhouse Ventilation Calculator

19,200 cubic feet of air, moved every minute. That is what summer ventilation asks of the exhaust fans in a 25-by-96-foot greenhouse — and it is why sizing a fan by the greenhouse’s square footage alone so often leaves plants cooking in a house that looks well equipped.

This calculator gives you the fan size your greenhouse actually needs: how much air to move in summer, in the shoulder seasons, and in winter, plus how much open vent area the fans need to breathe.

The calculator

Average height means the height of the air volume, not the peak of the roof. Eight feet is the standard working figure for most houses.

 

What do I type?

Measure the inside length and width in feet. For height, use 8 feet unless your house is clearly taller or shorter through most of its volume.

A hoop house with a high peak and low sides still averages out near its eave height plus a little. When in doubt, 8 feet is the figure the worked example below uses too.

What does this number mean?

The summer figure is the total exhaust fan capacity to shop for, in CFM — cubic feet per minute, how much air a fan moves. It aims for one full change of the greenhouse air every minute, which holds the inside about 8 degrees Fahrenheit above the outside air on a sunny day.

The shoulder-season figure is three quarters of the summer rate, and the winter figure is one quarter. Staging two or three smaller fans, instead of one large one, lets the house run at those lower rates without short-cycling a single big fan.

The inlet figure is the open vent or louver area the fans need: about 1.5 square feet of inlet for every 1,000 CFM of fan capacity. Starved inlets are the quiet reason many fans move far less air than their rating promises. Choose fans rated by AMCA, the Air Movement and Control Association, since unrated fans can move only 60 to 70 percent of their claimed flow against real resistance.

Worked examples

A 25-by-96-foot house at 8 feet tall holds 19,200 cubic feet of air. One change a minute means 19,200 CFM of fan capacity in summer, 14,400 CFM in the shoulder seasons, and 4,800 CFM in winter, with about 28.8 square feet of inlet opening.

A 10-by-12-foot hobby house at 7 feet holds 840 cubic feet. It needs 840 CFM in summer, 210 CFM in winter, and about 1.26 square feet of inlet.

Greenhouse (at 8 ft height)Summer CFMWinter CFM
6 x 8 ft38496
8 x 12 ft768192
10 x 12 ft960240
10 x 20 ft1,600400
12 x 24 ft2,304576
25 x 96 ft19,2004,800

The hand method matches the calculator: multiply length by width by height for the air volume, and that volume is the summer CFM. Take three quarters of it for the shoulder seasons and one quarter for winter.

What this calculator does not do

It sizes exhaust fans for ventilation only. It does not size evaporative cooling pads or heaters — heater sizing has its own calculator on this site — and it does not design natural ventilation, though a house in a mild climate may need fans only as backup.

For the heating companion, see the Greenhouse Heater Sizing Calculator. For structures, see Are Vevor Greenhouses Worth It?

Sources

University of Georgia Extension Bulletin 792, Greenhouses: Heating, Cooling and Ventilation — https://openscholar.uga.edu/record/23253/files/B792.pdf (fetched November 22, 2026).

UMass Extension, Ventilation for Greenhouses — https://www.umass.edu/agriculture-food-environment/greenhouse-floriculture/fact-sheets/ventilation-for-greenhouses (fetched November 22, 2026).